(2) Error code list (D000
When an error occurs, the ERR. LED does not turn on. The D LINK LED flashes or turns off.
Troubleshoot the problem with the CC-Link IE Field Network diagnostics. (
Error code
Error name
(hexadecimal)
Station type
D0E0
H
mismatch
Own station
D0E1
H
reserved
Station No.
D0E2
already in use
H
(own station)
Own station No.
D0E3
H
out of range
Transient data
D217
H
command error
Receive buffer
D2A0
H
full
Transient data
D2A3
H
length error
Station number
switch out of
D72A
range (a value
H
other than 1 to
120)
Transient data
DF01
H
divided error
When multiple errors occur, only the latest error code is stored in Error code (RWr0) or Warning code (RWr1).
The errors that have occurred before can be checked with the error history of GX Works2.
For error history, refer to the following.
• Checking by executing a command of the slave station (
• Error history data
to DFFF
(D529
H
H
Description and cause
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The transient data request
command is incorrect.
The target station is overloaded
and cannot receive transient
data.
The received transient data is
incorrect.
A station number out of range
has been set.
The divided transient data have
been received.
(address: 0A00
to 0AEF
H
CHAPTER 11 TROUBLESHOOTING
and D52B
excluded))
H
H
Page 102, Section 8.12)
Action
In the network configuration settings of the master station,
change the station type to that of the remote device station.
• In the network configuration settings of the master station,
cancel the reserved station setting.
• Change the station number of the module to a station number
that is not reserved.
• Set a unique station number.
• After taking the above action, turn off and on or reset all the
stations where this error has been detected.
Add the station information of the module in the network
configuration settings of the master station.
Correct the request command at the request source, and retry
the operation.
• Check the network status using the CC-Link IE Field Network
diagnostics of GX Works2.
• When the target station is overloaded and cannot receive
transient data, send the data to the target station after a while.
Correct the number of data (frame length) at the request source,
and retry the operation.
Set the station number within the allowable range.
Set the transient data size within the range that can be handled
by the module. Then send the transient data that is not divided.
Page 116, Section 11.1 (1))
) (
Page 148, Appendix 3 (14))