Mitsubishi NZ2GF2B-60DA4 User Manual page 140

Cc-link ie field network digital-analog converter module, programmable controller
Table of Contents

Advertisement

(5) CH
Digital value (RWw2 to RWw5)
On this area, the digital value for D/A conversion is written, in signed 16-bit binary, from the CPU module.
Output range setting
Setting range (Actual range)
0:
4 to 20mA
1:
0 to 20mA
2:
1 to 5V
3:
0 to 5V
4:
-10 to 10V
5:
User range setting 1
(-10 to 10V)
6:
User range setting 2
(0 to 20mA)
*1
The setting range and the actual range of when the scaling function is enabled depend on the settings in the scaling
upper limit value and the scaling lower limit value.
(a) When a value out of the setting range is written
D/A conversion is performed with the upper and lower limit value of the setting range. Simultaneously, the
following status notifies that the setting is out of the range.
• The check code is stored in CH
For details on check codes, refer to the following.
Page 136, Appendix 2 (3)
• The error code (060 ) for an out-of-range digital value is stored in Latest warning code (RWr1).
• Warning flag (RX7) turns on.
• The ALM LED flashes.
(b) Default value
The default value is set to 0 for all channels.
138
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
Sign bit
1: Negative
0: Positive
When the scaling function is disabled
-288 to 12287
(Actual range: 0 to 12000)
-16384 to 16383
(Actual range: -16000 to 16000)
-12288 to 12287
(Actual range: -12000 to 12000)
-288 to 12287
(Actual range: 0 to 12000)
b4
Data area
Digital value when a value out
of the setting range is written
12288 or more: 12287
-289 or less: -288
16384 or more: 16383
-16385 or less: -16384
12288 or more: 12287
-12289 or less: -12288
12288 or more: 12287
-289 or less: -288
Set value check code (RWr2 to RWr5).
b3
b2
b1
b0
When the scaling function
is enabled
Setting range
-32768 to 32767
(Maximum actual range: -32000
to 32000)
*1