Mitsubishi NZ2GF2B-60DA4 User Manual page 122

Cc-link ie field network digital-analog converter module, programmable controller
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
0130
Moderate error
H
0140
Minor error
H
0160
Minor error
H
017
Moderate error
H
0180
Moderate error
H
*1
Moderate error
040
H
*1
Minor error
060
H
120
Error name
Description and cause
Non-volatile
The parameter data stored in the
memory data
non-volatile memory are
error
abnormal.
(parameter)
Non-volatile
The error history data stored in
memory data
the non-volatile memory are
error (error
abnormal.
history)
A buffer memory area other than
Remote buffer
the remote buffer memory areas
memory
has been accessed using the
access error
REMFR/REMTO instruction.
An address other than those
assigned to the extension I/O
module for the external signal
assignment function has been
External signal
set.
assignment
represents one of the following
setting error
error types.
2: Alert output function
3: Error output
4: Warning output
Same address
The same address has been set
for the external
in multiple extension output
signal
modules for the external signal
assignment
assignment function.
function
The user range setting value has
been set to a value where the
Offset/gain
offset value is equal to or greater
setting value
than the gain value.
inverted
represents the channel
number where an error has
occurred.
The value set in CH
value (RWw2 to RWw5) is
Digital value
outside the range.
outside the
represents the channel
range
number where an error has
occurred.
• Set no request (0), request (1), and no
request (0) in Parameter information clear
request (address: 1002H) and set the
parameters of the non-volatile memory to
default.
• Set the parameters again.
• Take measures against noise with a
shielded cable for connection.
• If this error persists, the module may be in
failure. Please consult your local Mitsubishi
representative.
• The module will be automatically recovered
immediately after the error occurs. Note
that the error history of the errors that have
occurred will be lost.
• Take measures against noise with a
shielded cable for connection.
• If this error persists, the module may be in
failure. Please consult your local Mitsubishi
representative.
Correct the setting data of the
REMFR/REMTO instruction to access the
remote buffer memory.
Set an address that has been assigned to the
extension I/O module for the external signal
assignment function.
Set a unique address.
Correct the setting so that the offset value is
smaller than the gain value.
Digital
Set the value of CH
RWw5) within the allowable range.
Action
Digital value (RWw2 to