(4) Setting example of when both the scaling function and shift function are used
When the following settings are used for a channel with output range of 0 to 5V:
Ex.
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 9000
• "CH
Scaling lower limit value": 3000
• CH
Shifting set value (RWw6 to RWw9): -25
The digital value is as follows:
1) Digital value
(before adjustment)
Add the shifting set value.
2) Digital value + Shifting set value
(after adjustment)
Scale conversion
3) Scale converted value
Analog output
voltage (V)
0
1
2
3
4
5
Analog output voltage (V)
5
2) Digital value +
Shifting set value
(after adjustment)
3) Scale
converted
value
0
0
3000
3025
Digital value + Shifting set
Digital value
3025
4225
5425
6625
7825
9025
CHAPTER 8 FUNCTION
Add the shifting set value.
1) Digital value
(before adjustment)
Digital value
9000 9025
12000
Value after scaling
value
3000
4200
5400
6600
7800
9000
8
0
2400
4800
7200
9600
12000
87