Mitsubishi NZ2GF2B-60DA4 User Manual page 144

Cc-link ie field network digital-analog converter module, programmable controller
Table of Contents

Advertisement

(3) Warning flag assignment (address: 0006
Warning flag (RX7) is assigned to the remote output (RY) of the extension output module using the external
signal assignment function. When a minor error occurs, the assigned remote output (RY) turns on.
(a) Setting range
The remote output (RY) number of the extension output module, counted from the start remote output (RY)
number (0000
The following is an example for assigning Warning flag (RX7) to the remote output (RY) number, 6
Ex.
the extension output module.
The remote output (RY) number, 6
the main module.
Thus, set 26
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(c) Default value
The default value is set to No assignment (FFFF
If a value out of the setting range is set, an error occurs. The error code (0174
flag (RXA) turns on, and the ERR. LED turns on. The operation is performed in the previous setting.
142
) of the main module, is set.
H
Main module
0
to
H
for Warning flag assignment (address: 0006
H
)
H
Extension module
0
to
6
H
H
1F
20
to
26
H
H
H
, is 26
when counted from the start remote output (RY) number of
H
H
).
H
).
H
to
F
H
to
2F
H
) is stored in Latest error code (RWr0), Error
H
, of
H