(b) Noise filter (power supply line filter)
A noise filter is a component which has an effect on conducted noise. Attaching the filter can suppress more
noise. (The noise filter has the effect of reducing conducted noise of 10MHz or less.)
Connect a noise filter to the external power supply of a main module and the external power supply of an
extension module. Use a noise filter with the damping characteristics equivalent to those of MA1206
(manufactured by TDK-Lambda Corporation). Note that a noise filter is not required if the module is used in
Zone A defined in EN61131-2.
The precautions for attaching a noise filter are described below.
• Do not bundle the cables on the input side and output side of the noise filter. If bundled, the output side
noise will be induced into the input side cables from which the noise was filtered.
Filter
Noise will be induced when the input
and output wires are bundled.
• Ground the noise filter grounding terminal to the control panel with the shortest cable possible (approx.
10cm).
Input side
Input side
(power supply side)
(power supply side)
Induction
Output side
(device side)
Filter
Output side
(device side)
Separately install the input and
output wires.