Mitsubishi NZ2GF2B-60DA4 User Manual page 102

Cc-link ie field network digital-analog converter module, programmable controller
Table of Contents

Advertisement

(4) Setting procedure
When setting the assignment explained in the previous page
Ex.
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Field Configuration]
2.
Set "CH
3.
Set "CH1 Alert output setting" to "0: Enable".
4.
Set values for "CH1 Alert output upper limit value" and "CH1 Alert output lower limit value".
5.
Set 0x002A ("2A" of RY2A) for "Alert output signal assignment".
● Signals other than remote I/O signals assigned to the external module cannot be set with the external signal assignment
function.
If the above is set, the error code (017
LED turns on.
● Multiple remote I/O signals of the main module cannot be assigned to a remote output signal of the extension module.
If the above is set, the error code (0180
LED turns on.
● The external signal assignment function cannot be used together with the digital output HOLD/CLEAR function.
When "Digital output HOLD/CLEAR setting" is set to "1: HOLD", the setting is ignored and the D/A converter module
operates with "0: CLEAR" set.
100
[Parameter Processing of Slave Station]
D/A conversion enable/disable setting" to "0: Enable".
) is stored in Latest error code (RWr0), Error flag (RXA) turns on, and the ERR.
H
) is stored in Latest error code (RWr0), Error flag (RXA) turns on, and the ERR.
H
Select a D/A converter module in "List of stations"
[CC IE