Example setting of parameters
The following shows mechanical specifications and parameter settings required for configuring the system shown as the
application example. The parameter settings are examples for a 7.5 kW motor and the 11 kW inverter used for the winding
roller.
Item
Minimum roll diameter
100 mm
Maximum roll diameter
300 mm
Gear ratio
1/1.2
Maximum speed of the
400 m/min
actual line
Pr.
Parameter name
7
Acceleration time
8
Deceleration time
9
Electronic thermal O/L relay
DC injection brake operation
10
frequency
DC injection brake operation
12
voltage
Operation panel main monitor
52
selection
71
Applied motor
73
Analog input selection
80
Motor capacity
81
Number of motor poles
83
Rated motor voltage
84
Rated motor frequency
95
Online auto tuning selection
128
PID action selection
129
PID proportional band
130
PID integral time
134
PID differential time
158
AM terminal function selection
180
RL terminal function selection
181
RM terminal function selection
182
RH terminal function selection
184
AU terminal function selection
189
RES terminal function selection
193
OL terminal function selection
194
FU terminal function selection
Specification
Setting value
Initial
Intermediate
value
roller
15 s
0 s
15 s
0 s
Inverter
rated
0
current
3 Hz
0.5 Hz
4%
2.5%
0
27
0
30
1
1
9999
7.5 kW
9999
4 (poles)
200 V
164 V
9999
51 Hz
0
0
0
40
100%
9999
1 s
9999
9999
9999
1
26
0
114
1
1
2
2
4
4
62
62
3
237
4
238
Item
Initial roll diameter
Disabled
calculation
Roll diameter storage
Enabled
Tension command
0 to 300 N
Tension setting output
Required
Winding
roller
0 Hz
Set "22" (Roll diameter) or "27" (Actual line
speed) for monitoring.
Or use any of Pr.774 to Pr.776 when using the 3-
line monitor screen on the PU.
Other monitor items related to this application and
22
their setting values are as follows:
26 (Line speed command), 81 (Tension command
after taper compensation), 82 (Winding diameter
compensation torque command), 83 (Inertia
compensation), and 84 (Mechanical loss
compensation).
30: Setting for the Mitsubishi Electric Vector
control dedicated motor SF-V5RU.
10: Terminal 2 input between 0 to 10 V for the line
10
speed with reversible polarity.
Set these parameters according to the motor.
2
2: Magnetic flux observer (continuous tuning)
0
100%
1 s
9999
26 (for intermediate roller): Line speed command
1
value
114: Tension control selection (X114) signal ON
(Setting "114" is required for tension control.)
109: Stored winding diameter clear (X109) signal
109
ON (Setting "109" clears the stored roll diameter.)
123: Stall mode trigger signal (X123) signal ON
123
(Setting "123" triggers the stall mode.)
To use the inertia compensation function, assign
111
the Inertia compensation acceleration (X111)
signal and the Inertia compensation deceleration
112
(X112) signal.
To use the inertia compensation function, assign
3
the Line speed acceleration (Y237) signal and the
Line speed deceleration (Y238) signal to affected
output terminals on the inverter for the
4
intermediate roller to output these signal to the
inverter for the winding roller (shaft).
Application examples
Specification
Remarks