Operation
Use the NEXT key to move through the
devices until you display the ones whose
LEDs you wish to test. Follow the instruc-
tions above.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Test menu.
To turn on a device LED for a different
module, select DEVICE_ LED from the
Test menu and follow the preceding
instructions.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)
Test: MOI Lamp Test
Use MOI_lamp_test to test the MOD-16
outputs of an MOI-7.
From the Test menu, use the Left or Right
arrow key to cause the M in MOI to start
blinking:
TEST: DEVICE LED MOI Lamp Test
(If you press HELP at this point, the System
displays:
TO TEST MOI-7 / MOD-16 LAMPS
Press HELP again to return to the above
menu.)
Press ENTER when the M is blinking to
select MOI_LAMP_TEST.
The System asks you to type the module
number. Type the three-digit module
number and press ENTER. (Enter all
leading zeros.)
If the MOI-7 module is present in CSG-M
the MOD-16 outputs will be placed in a 30-
second lamp test mode. After 30 seconds,
these outputs return to their previous state.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)
3-46
Test: Network
(X-Network, M-Network)
This function is used only by Siemens
Industry, Inc., engineers to observe network
traffic so that they can evaluate the operation
of the module communication network.
Test: Override
Use Test Override to override the CSG-M
selected options for Alarm Verification and
Alarm Confirmation.
From the Test menu, use the Left or Right
arrow key to cause the O in OVERRIDE to
start blinking.
(If you press HELP at this point, the System
displays:
OVERRIDE ALARM VERIFY & CONFIRM
Press HELP again to return to the above
menu.)
Press ENTER when the O in OVERRIDE is
blinking and the menu displays:
OVERRIDE: ALR VERIFY ALR CONFIRM
Use the Left or Right arrow key to switch
between ALR_VERIFY and ALR_CONFIRM.
Override the Alarm Verification CSG-M
Selection
From the Override menu, press ENTER
when the A in ALR_VERIFY is blinking to
select Alarm Verification.
The System shows the following menu:
OVERRIDE: YES NO
A blinking Y in YES indicates that Alarm
Verification Override is currently enabled. A
blinking N in NO indicates that the Alarm
Verification Override is currently disabled.
To enable Alarm Verification Override, use
the Left or Right arrow key to cause the Y
in YES to start blinking. Pressing ENTER
when the Y in YES is blinking will cause
Alarm Verification Override to be enabled.