With each press of NEXT, the System
continues to display module types through
number 255, the highest module number
allowed by the System. It then returns to
the List menu.
Print the Module Type and Network Address of
All Modules
Press PRINT when the M in MOD_ TYPE is
blinking to print a full list of module types
and their Network addresses. The System
prints a list similar to the following:
Listing of Module Types:
1- V7 ALD
2- V7 ALD
3- V4 CZM-4
251- V5 MKB-4
253- V1 MXL-IQ Panel
In the above display, the number following
the V (for example, V7) is the software
version number of the software installed in
the module.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Device Type

Use List Device Type to show the type of a
particular device.
From the List menu use the Left or Right
arrow key to cause the D in DEV_TYPE to
start blinking:
LIST: VOLTAGES MOD TYPE DEV TYPE
(If you press HELP at this point, the System
displays:
SHOW THE TYPE OF DEVICE
Press HELP again to return to the List menu.)
Display the Device Type of a Specified Device
Press ENTER when the D is blinking to
select LIST DEV_TYPE.
The System asks you for a module and
device number:
TYPE IN MODULE & DEVICE:
Type the three-digit module number and
three-digit device number using the nu-
meric keypad and press ENTER. (Enter all
leading zeros.) The System displays the
device type for the address specified:
004-001 TYPE: [device type]
If you press NEXT, the System displays the
device type for the next device in the
sequence:
004-002 TYPE: [device type]
With each press of NEXT, the System
continues to display device types until there
are no more devices for that module. The
System then returns to the List menu. To
proceed to another module, follow the
preceding instructions.
Print a List of Devices Assigned to a Specified
Module
Press PRINT when the D is blinking to
select LIST DEVICE. The System asks you
for a module number:
TYPE IN MODULE NUMBER:
Type only the module number and press
PRINT. (Enter all leading zeros.) The
System prints a list of all device types
assigned to the specified module in a
format similar to the following:
Listing of Device Types Module 1 (ALD):
1-TRI-D Dual Switch Input
2-TRI-D Dual Switch Input
4-TRI-D Switch input + Relay
5-TRI-S Switch Input
7-TRI-S Switch Input
10-ID-60T-135 Thermal Detector
11-ID-60T-135 Thermal Detector
15-ID-60I Ionization Detector
16-ID-60I Ionization Detector
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)