Trouble Message
Signal Mod A/D Convert Fail
Signal Module Zone Code
Software Key Violation
Stack Fault Call Support
Style 4 Network Mode
Style 7 Network Mode
System Commissioning Mode
System Signal Power Failure
Tamper Switch
Too Many ALD-2s
Trouble Causing Input
Trouble Type Not Defined
Troubles Summarized
Unspecified Dev Responding
The Probable Cause Is:
The CSM-4 at this address has a failed
analog-to-digital converter.
Zone code failure on the CSM-4 module.
Incorrect Software Key Installed (NCC
only).
When the message Call Support appears,
a four letter Alpha ID will be displayed. This
number is necessary when reporting the
problem to Siemens Industry, Inc.
The Style 4 jumper on a NET-7 is found on
a Style 7 system. Move the jumper to the
Style 7 position.
The Style 7 jumper on a NET-7 is found in
the Style 4 mode. Move the Style 7 jumper
to the Style 4 position.
The system has been put in the commis-
sioning mode.
A CSM-4 has lost power to its output
circuits.
This is a security-type message for the
tamper switch on the SMB-2 board when
the system is selected for UL 1076 operation.
To many ALD-2Is are installed on the system.
This is beyond the maximum allowed.
A device programmed on the system as
trouble causing has been activated and has
changed state.
Unspecified trouble has been received from
this address.
While the system is in the commissioning
mode, the modules will display this message
in lieu of all the devices on this module.
An analog device has reported at an
address not assigned in CSG-M.
Appendix J
J-7