7.5.2 Test

7.5.2.1 Detection test
Building Technologies
Fire safety
This function sets a section or a zone to 'Test' mode. The panel provides two kinds
of test modes:
Silent: All sounders remain silent in fire alarm condition during testing. Only the
LCD screen displays the test event.
Audible: All sounders sound for a period of 10 seconds in fire alarm condition
during testing. The LCD screen displays the test event.
The procedure below indicates how to set a section to 'Test' mode as an example.
Set a section to 'Test' mode
1. Press
on the keypad, the 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
7 - Logout
8 - Query alarm counter
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
3. Select 'Test' and press
Test
1 - Detection test
2 - Lamp test
L2
, the 'Operation' window is open.
L2
, the 'Test' window is open.
L2
Operation
7
Access level 2
73 | 124
A6V10421795_en--_g
2016-11-18