Appendix E
With Device Confirmation, the B C
verification time known as System Justi-
fied Alarm time is also adjustable. It is the
same time used by both ionization and
photo detectors. If a device is individually
selected for alarm verification, the alarm
verification feature takes priority over the
device confirmation option. For adjustment
ranges, refer to the CSG-M Programming
Manual, P/N 315-090381.
E-2
There is an Override menu selection in the
Test menu of MXL-IQ. Select Alr_Verify to
disable all alarm verification or select
Alr_Confirm to disable all alarm confirma-
tion for a period of up to 4 hours or until
manually re-enabled.