Access Level 2; Manned / Unmanned; Silence / Resound; Led, Display And Buzzer Test - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

6.4
6.4.1
Information
Manned operation
Manned mode
activated
6.4.2
6.4.3
48
Smart Infrastructure

Access level 2

Operation is available with password or key switch.

Manned / unmanned

In case of attendance switch the fire control panel to manned operation.
2
1/1

Silence / resound

Sounders are activated in the event of a fire alarm.

LED, display and buzzer test

Test the panel indication.
Press the <MANNNED / UNMANNED> button to
toggle.
Manned mode – LED ON
Unmanned mode – LED OFF
Press the <SILENCE / RESOUND> button to
silence the sounders.
It is possible to reactivate the sounders in the
event of a fire alarm at any time.
Every new alarm event will reactivate the
sounders again, if programmed.
Optional: The sounders can be activated at any
time 'Toggle function' (no alarm event is required)
if programmed.
Press the button <LAMP TEST> and all LEDs, the
display and the internal buzzer are activated for a
period of 5 seconds.
A6V10393190_h_en_--
2019-09-01