List Percent/Ft - Senstvty; List Percent/Ft - Pre-Alarm; List Percent/Ft - Analog; List: Asd_Apps - Siemens MXL-IQ Operation, Installation, And Maintenance Manual

Table of Contents

Advertisement

LIST: PERCENT/FT
Press ENTER to select List Percent/ft. The
System asks you for a module and device
number.
TYPE IN MODULE & DEVICE: 001-001
Type in the three-digit module number and
the three-digit device number using the
numeric keypad and press ENTER. The
System displays the following menu for that
device (the S in Senstvty will be blinking):
002-003 SENSTVTY
PRE-ALARM
List Percent/ft – Senstvty
The display for Sensitivity supplies the
current sensitivity as read back from the
detector and is similar to the following
(readings are dynamic):
002-003 SENS 1.4%/FT
List Percent/ft – Pre-alarm
The display for Pre-alarm supplies the
current Pre-alarm setting read back from
the detector and is similar to the following
(readings are dynamic):
002-003 PRE-ALARM 1.4%/FT
List Percent/ft – Analog
The display for Analog supplies the current
analog2 reading read from the detector and
is similar to the following (readings are
dynamic):
002-003 SENS 1.4%/FT
To leave the Percent/ft menu without going
through all subaddresses, press the Up
arrow key. The System displays the List
menu.
Print the Analog Loop's Current Readings in
Percent/ft Obscuration
Press PRINT when the P in Percent/ft is
blinking. The System asks you for a module
number.
TYPE IN MODULE NUMBER:
Type the three-digit module number using
the numeric keypad and press ENTER. The
System shows the following menu for that
device (the S in Senstvty will be blinking):
001-001 SENSTVTY PRE-ALARM ANALOG
ANALOG
The System prints either the Sensitivity, Pre-
alarm, or Analog of all the devices for the
specified module in a format similar to the
following (NA = ID-60 detector):
%/ft SENSITIVITIES FOR MODULE 2
1-3.00 2-NA
6-1.4
11-ND
NORM
16-ND
21-ND
26-ND
31-ND
36-ND
41-ND
46-ND
51-ND
56-ND
NORM

List: ASD_apps

Use List ASD_apps to display operational
characteristics of the ASD devices.
From the List menu use the left or right
arrow key to cause the A in ASD_Apps to
start blinking:
LIST: ASD APPS
NORM
Display the Operational Characteristics of One
Device
Press ENTER to select ASD_apps. The
System asks you for a module and device
number:
TYPE IN MODULE & DEVICE:
3-1.4
4-3.1
7-ND
8-ND
9-ND
12-ND
13-ND
14-ND
17-ND
18-ND
19-ND
22-ND
23-ND
24-ND
27-ND
28-ND
29-ND
32-ND
33-ND
34-ND
37-ND
38-ND
39-ND
42-ND
43-ND
44-ND
47-ND
48-ND
49-ND
52-ND
53-ND
54-ND
57-ND
58-ND
59-ND
5-1.4
10-ND
15-ND
20-ND
25-ND
30-ND
35-ND
40-ND
45-ND
50-ND
55-ND
60-ND
Operation
3-35