Siemens MXL-IQ Operation, Installation, And Maintenance Manual page 47

Table of Contents

Advertisement

Test
1. Observe the display on the MKB-4.
2. Activate every alarm causing initiating
device on the System in groups of 100 or
fewer. Reset the System prior to
activating each group of 100.
3. Activate all supervisory devices on the
System.
4. Activate all security devices on the
System.
• The POWER LED should be on steady.
• The TROUBLE LED should be off.
• The following message should appear on the alphanumeric
display:
(Time and Date)
(Time and Date)
(Time and Date)
(Time and Date)
(Time and Date)
(System Custom Message)
(System Custom Message)
(System Custom Message)
(System Custom Message)
(System Custom Message)
(It may take a few minutes after power-up before the message
System Normal appears.)
• Every device alarms and there are no troubles annunciated.
• Device LEDs should come on when the device is in alarm.
• As each device is alarmed, the custom message appears on the
display, is recorded on the printer (if installed), and corresponds
to the CSG-M printout for that device.
• The messages listed on the printer are in the order in which the
devices were alarmed.
• Pressing the NEXT key on the MKB-4 displays the devices in
reverse order.
• Check that all appropriate responses are activated.
• Each device should cause a supervisory.
• As each device changes state, the custom message appears on
the display, is recorded on the printer (if installed), and corre-
sponds to the CSG-M printout for that device.
• The messages listed on the printer are in the order in which the
devices were activated.
• Pressing the NEXT key displays the devices in reverse order.
• Check that all the appropriate responses are activated.
• Each device should cause a security condition.
• As each device is activated, the custom message appears on
the display, is recorded on the printer (if installed), and corre-
sponds to the CSG-M printout for that device.
• Check that all appropriate responses are activated.
Response
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
Installation
2-17