Operation
3-2

System Modules

ALD-2I Analog Loop Module
The ALD-2I takes two adjoining module
addresses. Loop 1 of the ALD-2I is at any
module address and loop 2 at the next
address. The analog loops on the SMB-2
are at module addresses 1 and 2 (See
Table 17, page 3-1) and cannot be moved.
The table below illustrates ALD-2I module
addresses:
ALD at Module
Addresses 3 and 4
Loop 1
Loop 2
ALD at Module
Addresses 15 and 16 Devices
Loop 1
Loop 2
CSM-4 Signal Module
The CSM-4 module contains two circuits
and two programmable LEDs.
Their device addresses on the module are
as follows:
Circuit 1
Circuit 2
LED 1
LED 2
For example, the address of circuit 2 on the
CSM-4 at module address 3 is 003-002.
CRM-4 Relay Module
The CRM-4 Relay module contains four
relays and two controllable LEDs.
Their device addresses on the module are
as follows:
Relay 1
Relay 2
Relay 3
Relay 4
LED 1
LED 2
For example, the address of relay 4 on the
CRM-4 at module address 20 is 020-004.
CZM-4 Conventional Zone Module
The CZM-4 Conventional Zone module
contains four conventional initiating device
zones and two programmable LEDs. Their
device addresses on the module are as
follows:
Devices
003-001 to 003-060
004-001 to 004-060
For example, the address of zone 1 on the
CZM-4, at module address 105, is 105-001.
015-001 to 015-060
MKB Keyboard/Annunciator
016-001 to 016-060
The MKB Keyboard/Annunciator occupies
the fixed module address 251 (See Table
17, page 3-1).
SMB-2 Main Board
The SMB-2 occupies module addresses 1,
2, and 253. The module addresses 1 and 2
are analog loops.
001
Module address 253 contains two notifica-
tion appliance circuits (NACs) and two
002
relays. The device addresses at module
005
253 are as follows:
006
For example, the address of the common
alarm relay at module address 253 is
253-001.

Remote System Modules

001
MOI-7 Voice and Annunciator Driver
002
The MOI-7 occupies one network address
003
and one network node in the MXL-IQ
System. Set the address on S1 (See Figure
004
17, page 1-10) according to Table 16, page
005
2-19, so that it agrees with the address
assigned in CSG-M.
006
The MOI-7 has a set of 128 subaddresses
reserved for the MOD-16 open collector
Zone 1
001
Zone 2
002
Zone 3
003
Zone 4
004
LED 1
005
LED 2
006
Common alarm relay
Common trouble relay
NAC 1
NAC 2
001
002
004
005