Operation
If you enter any address for which there is
no device assigned, the System displays:
NO DEVICE ASSIGNED
Press ENTER while the S in SENSTVTY is
blinking to select CONTROL SENSTVTY.
The System asks you for a module number
and device number:
TYPE IN MODULE & DEVICE:
Type the three-digit module number and
three-digit device number using the nu-
meric keypad and press ENTER. The
System shows the following display:
001-001 Norm Hi 1 Hi 2 Hi 3
The current sensitivity setting is highlighted.
The System offers you a choice of seven
levels of sensitivity: Hi_3, Hi_2, Hi_1, Norm,
Low_1, Low_2 or Low_3. Use the Right and
Left arrow keys to highlight the level you
wish to set for the smoke detector specified
and press ENTER. The System makes the
change in sensitivity setting.
Press NEXT to move through the devices
until you display the ones you want to
change, and follow the instructions above for
making the changes.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Control menu.
You can select another address by select-
ing SENSTVTY and following the instruc-
tions above.
To leave the Control Sensitivity displays
without going through the entire list, press
the Up arrow key. The System displays the
Control menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
3-38

Control: Arm/dis

Use Control Arm/dis to enable or disable
the operation of an initiating device.
From the Control menu, press the Left or
Right arrow key to cause the A in ARM/DIS
to start blinking.
(If you press HELP at this point, the System
displays:
DISARM OR ARM DEVICES
Press HELP again to return to the Control
menu.)
Press ENTER while the A in ARM/DIS is
blinking to select Control Arm/dis.
The System asks you for the module
number and device number of the detector
you wish to arm or disarm. Type the three-
digit module number and three-digit device
number using the numeric keypad and
press ENTER. (Enter all leading zeros.)
The System displays:
001-001 ARM DISARM
The System offers you a choice of arming
or disarming the device. Use the Right and
Left arrow keys to highlight your choice and
press ENTER. The System makes the
change.
When you disarm an input device, the
System automatically annunciates the
disarming as a Trouble and lights the
PARTIAL SYSTEM DISABLE LED.
Press NEXT to move through the devices
until you display the ones you want to
change; follow the instructions above for
making the changes.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Control menu. To
arm or disarm another module device,
select ARM/DIS and follow the preceding
instructions.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)