Walktest Ending Sequence - Siemens MXL-IQ Operation, Installation, And Maintenance Manual

Table of Contents

Advertisement

1. When the System is in the audible
Walktest mode, all silenceable and non-
silenceable audibles that are not already
active or disarmed sound the code,
depending on how the device is used in
the CSG-M. The codes are as follows:
E
V
E
N
T
C
O
L A
R A
M
2
s
S
U
E P
V R
S I
O
Y R
2
n o
R T
O
B U
E L
4
s
S
C E
U
I R
Y T
4
n o
T S
T A
S U
O /
H T
R E
6
s
2. When a printer is installed, the printer
prints a message similar to the following:
WLK [event type] IN/OUT device
WLK [event type] IN/OUT device
WLK [event type] IN/OUT device
WLK [event type] IN/OUT device
WLK [event type] IN/OUT device
address time/date device type,
address time/date device type,
address time/date device type,
address time/date device type,
address time/date device type,
custom message, trouble type
custom message, trouble type
custom message, trouble type
custom message, trouble type
custom message, trouble type
(if applicable)
(if applicable)
(if applicable)
(if applicable)
(if applicable)
3. The LCD displays the device address,
custom message, WLK IN/OUT [event
type], and device type for 8 seconds.
4. If the ALD device has an LED, it turns on
for 30 seconds to provide additional
feedback to the technician.
If the MXL-IQ detects multiple events, they
are automatically spaced 8-10 seconds
apart to allow for separation of the coding.
Up to five simultaneous events may be
queued for processing.

Walktest Ending Sequence

NOTE: This sequence does not occur in
Silent Walktest.
When 5 minutes remain in Walktest, all
silenceable and non-silenceable audibles
that are not already active or disarmed cycle
on-off five times (1 second on) to indicate
that the Walktest will time out in 5 minutes.
This occurs in the audible mode only.
When 1 minute remains, event coding and
the processing of devices to the LCD are
suspended. If a device is alarmed, it is cycled
silently through the resetting sequence.
When 45 seconds remain, all silenceable
and non-silenceable audibles that are not
already active or disarmed cycle on-off until
Walktest times out. Do NOT continue to
walktest devices. This 45 second period
of no new Walktest events ensures that all
devices are reset when the Walktest timer
expires and the System returns to normal
D
E
operation. Alarming a device during this
period might result in the reporting of
c e
n o
s d
o
, n
h t
n e
f f o
erroneous events when the system
returns to normal operation.
- e
e s
o c
d n
u p
e s l
( s
n o
o -
) f f
c e
n o
s d
o
, n
h t
n e
f f o
NOTE: If an alarm or supervisory is
reported from a device that is NOT in
Walktest, the Walktest is suspended
- e
e s
o c
d n
u p
e s l
( s
n o
o -
) f f
immediately. No further Walktest events
c e
n o
s d
o
, n
h t
n e
f f o
are annunciated or coded. The Walktest
remains running in the background of the
MXL-IQ until it times out or is canceled.
Walktest Individual CZM-1B6 or CZM-4
Zone
To place an individual CZM-1B6 or CZM-4
zone in Walktest, follow the procedure
below:
WARNING:
When performing a partial system
Walktest, DO NOT TEST any devices
that are not in the Walktest as this will
cause an alarm in the system.
• Move the cursor to the Z in Zone wAUD
for a Walktest with audible feedback or
Z SIL for a silent Walktest.
• Press ENTER.
• The MXL-IQ prompts the user for the
module and device number to be tested.
• Enter the desired network address,
including all leading zeros, followed by
ENTER.
• If the network address entered is not a
CZM-4 or CZM-1B6 zone, the message
Invalid type for Walktest is displayed for
2 seconds on the LCD. The display then
returns to the Walktest menu.
• If the module type is a CZM-1B6 or
CZM-4 zone in the CSG-M, the following
events take place:
Walktest Operating Instructions
5-5