Siemens MXL-IQ Operation, Installation, And Maintenance Manual page 83

Table of Contents

Advertisement

List Air Sampling – Smoke_Lev
Press ENTER when the S in SMOKE_LEV
is blinking to select List AIR SAMPLING
SMOKE_LEV.
The System asks you for a module and
device number:
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The system displays the
smoke level for the address specified:
010-004 50% >>
!
The bar graph in the example above shows
the following information for the Air Sampling
device at address 010-004:
50% = 50% of full scale smoke level
!
= active trip point at 30%
*
= inactive trip point at 60% and 100%
PRE1 indicates the device is in PreAlarm 1
PRE2 and ALRM indicate the PreAlarm 2
and Alarm states, respectively. The bar-
graph continuously updates to reflect the
current state of the Air Sampling zone that
is being viewed.
Print the Air Sampling Smoke Level
Press PRINT when the S in SMOKE_LEV
is blinking to print the AIR SAMPLING
SMOKE_LEV.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1 (ASP) module
number and press ENTER. The System
sends smoke levels for all devices on the
selected MODULE to the printer.
Air Sampling Smoke Levels at 13:23:31 Jan 03, 20XX
010-001
13:23:31 Jan 03,20XX
0% Scale >>
.
.
010-002
13:23:32 Jan 03,20XX
100% Scale >> ! ! !<<
010-010
13:23:31 Jan 03,20XX
42% Scale >> !
.
.<< PRE1, Cust Msg 10
010-011
13:23:32 Jan 03,20XX
100% Scale >> ! !
.<< PRE2, Cust Msg 11
For printed bar graphs, the characters
shown below indicate the following:
List Air Sampling – Flow_Lev
Press ENTER when the F in FLOW_LEV is
blinking to select LIST AIR SAMPLING
FLOW_LEV.
The System asks you for a module and
device number:
TYPE IN MODULE & DEVICE
*
*<< PRE1
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The System displays
the air flow level for the address specified:
010-004 50% >> !
The bar graph in the example above shows
the following information for the Air Sampling
device at address 010-004:
NORM indicates that the current air flow
level is at a normal level, HIGH indicates
airflow is too high, and LOW indicates
airflow is too low. The bar graph continu-
ously updates to reflect the current state of
the Air Sampling zone that is being viewed.
Print the Air Sampling Flow Level
Press PRINT when the F in FLOW_LEV is
blinking to print the AIR SAMPLING
FLOW_LEV.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
.<< NORM, Cust Msg 1
Type the three-digit NIM-1 (ASP) module
number and press ENTER. The System
ALRM, Cust Msg
sends air flow levels for all devices on the
selected MODULE to the printer.
. = an inactive trip point
! = an active trip point
50% = 50% of full scale air flow level
!
= low air flow trip point at 20%
*
= high air flow trip point at 90%
* << NORM
Operation
3-33