Pre-alarm adjust
.25% / ft.
increment
Pre-alarm range
.25 - 2.0% / ft.
Pre-alarm
1.5% / ft.
default
Sensitivity adjust
~.25% / ft.
increment
Sensitivity range
1.25 - 3.4% / ft.
Sensitivity
3.0% / ft.
default (Norm)
Because the pre-alarm and sensitivity
settings overlap, set the pre-alarm to at
least an increment below the sensitivity
setting.
Field Programmer Use
The FPI-32 (Rev. 1.3 or higher) must be
used to enable the programming of the ILI
and ILP IDs. The IDs tell the smoke
detector it has the advanced features such
as pre-alarm. For more information about
using the FPI-32 with IL series detectors,
refer to the FPI-32 Programmer/Tester
Operations Manual, P/N 315-090077.
ION
.12% / ft.
.25 - .75% / ft.
.75% / ft.
~.12% / ft.
.6 - 1.6% / ft.
1.4% / ft.
Appendix M