ADDITIONAL OPERATING PROCEDURES

In addition to the basic fire alarm instructions above, several features are included to facilitate
maintenance and increase the versatility of the system. The following are procedures used to
initiate these functions.

Lamp Test

When selected, Lamp Test activates LCD, the buzzer and turns on all the LEDs on the user
interface, then back to its previous state.
To initiate a Lamp Test, proceed as follows:
Press "MENU".
On the MENU display, select "Oper".
Select "Lamp Test "to run.
Note that lamp test operates the indicators only on the units being operated and no record is
reported to system history.
The lamp test lasts 10 seconds. From 0 to 4 seconds LCD test; From 4 to 7 seconds LEDs
test; From 7 to 10 seconds buzzers test. Operator doesn't need to turn it off manually. Lamp
test will automatically quit when it completes.

History

The last 1000 system events are time-tagged and recorded for review in the user level event
history. This history and all user-level functions are available to users with the door key.
Operation of history:
New events overwrite old when filled.
For more information see the Event History section.
Access to history:
To recall past events, proceed as follows:
Press "MENU" button.
MENU" display, select "View".
On the "
• Select "History".
Operate up button adjacent to the LCD for previous event display.
Operate down button adjacent to the LCD for next event display.