MOD-16 Output Driver*

The MOD-16 Output Driver module is an
annunciator driver controlled by the MOI-7
module. Up to 8 MOD-16s can be used
with an MOI-7. Each MOD-16 can activate
up to 16 outputs for a total of 128 outputs.

MOI-7 Voice and Annunciator Driver*

The MOI-7 module is an MXL-IQ network
module that connects to a graphic annun-
ciator using MOD-16s or MID-16s.
The MOI-7 has two LEDs to indicate the
status of the MXL-IQ network interface:
• the TRANSMIT LED blinks when the
MXL-IQ/MOI-7 communication is
working
• the TROUBLE LED goes to steady
when MOI cannot communicate

MOM-2 Card Cage

The MOM-2 Card Cage contains 2 slots for
optional module cards; it can handle 2 half-
width cards or 1 full-width card. The MOM-2
provides 2 power-connector receptacles and
2 data-connector receptacles. A 24 VDC
cable that provides the main power used by
the optional modules, and an 8-wire ribbon
cable for connection of 5 VDC and data, are
provided with the MOM-2 installation kit.
Figure 20
MOD-16 Output Driver
Figure 21
MOI-7 Voice and Annunciator Driver
Figure 22
MOM-2 Card Cage