(If you press HELP at this point, the System
displays:
SHOW DETECTOR VOLTAGES
Press HELP again to return to the List menu.)
Display the Voltage of One Device
Press ENTER to select List Voltages. The
System asks you for a module number and
device number. Type the three-digit module
number and three-digit device number
using the numeric keypad and press
ENTER. (Enter all leading zeros.) The
System shows the following menu for that
device (the A in ANALOG will be blinking):
001-001 ANALOG THRESH SENS
Press ENTER to show the Analog voltage
for that device. When you ask for any
voltage, the System displays Please wait for
response until it receives a reading from
the device; if you have just reset the
System, it alternates the above message
with the message Device being initialized.
The display for Analog voltage is similar to
the following (readings are dynamic):
001-001 ANALOG2 = 2.75 VOLTS
Press ENTER to return to the previous
display. To view the Threshold or Sensitivity
voltage of any device listed, use the Right
and Left arrow keys to highlight the first
letter of the category desired and press
ENTER.
The display for Threshold voltage is similar
to the following:
001-001 THRESHOLD = 4.75 VOLTS
The display for Sensitivity voltage is similar
to the following (readings are dynamic):
001-001 SENSITIVITY = 2.62 VOLTS
Press the Up arrow key to return to the List:
Voltage Mod_type Dev_type menu.
If the module number entered is not an
analog loop, the System displays:
Not Analog Loop.
If the device address has no device as-
signed by CSG-M, the System displays:
No Device Assigned .
When displaying sensitivities, if the device is
not a smoke detector, the System displays:
Not a Smoke Detector .
Print the Voltage of All Devices Assigned to a
Specified Module
Press PRINT when the V in Voltages is
blinking. The System asks you for a module
number. Type the three-digit module number
and press ENTER. (Enter all leading
zeros.)
002-001 Analog Thresh Sens
Press ENTER to print the Analog voltage
for all devices assigned to the module
(ND = No Device).
ANALOG VOLTAGES FOR MODULE 1
1- 2.00 2- 2.00 3- ND
6- ND
7- ND
8- ND
11- ND
12- ND
13- ND 14- ND 15- ND
To print the Threshold voltages of all the
devices for the specified module, use the
arrow keys to cause the T in THRESH to
blink and press PRINT. The System prints
those threshold voltages in a format similar to
the following (ND = No Device):
THRESHOLD VOLTAGES FOR MODULE 1
1- 4.75 2- 4.75 3- ND
6- ND
7- ND
10- ND
11- ND 12- ND
13- ND 14- ND 15- ND
4- ND
5- ND
9- ND 10- ND
4- ND
5- ND
8- ND
9- ND
Operation
3-27