Control: Change Apps; Test Menu - Siemens MXL-IQ Operation, Installation, And Maintenance Manual

Table of Contents

Advertisement

Operation
Control Percent/ft - Pre-alarm
The display for Pre-alarm supplies the
current pre-alarm setting read back from
the detector and is similar to the following
(readings are dynamic):
002-003 PRE-ALARM .75%/FT
In the previous message, 002-003 is the
address. Pre-alarm is the type of response
(Sensitivity or Pre-alarm). .75%/ft is the
smoke detector reading in %/ft obscuration
and Norm is the text sensitivity range
corresponding to the %/ft readings.
Use the left and right arrow keys on the
keypad to lower or raise the %/ft reading.
(Refer to the Sensitivity and Pre-Alarm
Settings chart.)
After you change the pre-alarm setting, the
System prints the information for the
selected device in a format similar to the
following:
CMD CHANGE PRE-ALM 06:38:20 JUN 2, 20XX
002-004 1.4%/FT NORM
NOTE: Because the pre-alarm and sensi-
tivity settings overlap, set the pre-alarm to
at least an increment below the sensitivity
setting.

Control: Change Apps

Use Control Change_Apps to change the
application of an ASD device.
From the Control menu, press the Left or
Right arrow key to cause the C in
Change_Apps to start blinking.
(If you press HELP at this point, the System
displays:
CHANGE DEVICE'S APPLICATIONS
Press HELP again to return to the Control
menu.)
Press ENTER while the C in Change_Apps
is blinking to select Control Change_Apps.
The System asks you for the module and
device number.
TYPE IN MODULE & DEVICE:
3-42
Type the three-digit module number and
three-digit device number using the nu-
meric keypad and press ENTER. (Enter all
leading zeros.)
Use the arrow keys to cycle through the 11
supported applications described in the
NORM
ASD Submenu Abbreviations on page I-1,
in Appendix I, and press ENTER to select
the desired application.
The transaction and the time that it occurs
will be printed on the printer as a confirma-
tion. The example shown below assumes
that no application is currently assigned to
module 001, device 001:
Control: Change_Apps Reset >
Type in Module & Device: 001-001
module-device number, including all leading zeros]
001-001 NONE OFFC WHSE LOBY > [Use arrow
keys to select the desired application]
001-001 NONE OFFC WHSE LOBY >
A statement will be printed out to confirm
the change:
COMMAND C C C C C HANGE_APPS 09:41:43 AUG 07,
20XX 001-001 NONE —> OFFC
To leave the Change_Apps menu at any
time, press the Up arrow key.
NOTE: If the ASD application is changed
while Test ASD is on, the changes will not
be effective until Test ASD is turned off.

TEST Menu

The Test menu has sixteen items from
which to choose; three of those items have
submenus, as follows (the shortened terms
used in the menu itself are in parentheses):
Set_time
Ground fault (GND_FLT)
Power*
Main
Voltage
Current
Lamp_test
LEDs
Display
[Press ENTER]
[Enter
[Press ENTER]