Appendix J
J-8
Trouble Message
Unspecified Mod Responding
Unspecified Node Responding
WALKTEST Activated
Warm Reset
Watch Dog Circuit Triggered
Zone Loop Open
Zone Loop Shorted
Zone Power Loss
The Probable Cause Is:
A module has reported at an address not
assigned in CSG-M.
• NIM-1W address on another node is
incorrect.
• The network CSG-M is incorrect.
The MXL-IQ has been placed in the walk
test mode.
The hardware reset input to the MXL-IQ
was used.
The watch dog circuit on the
SMB-2 triggered.
Broken wire on CZM-4 circuit.
Shorted wire on CZM-4 circuit.
The CZM-4 zone at this address has lost its
24 volt input.