Operation
Air Sampling Air Flow Levels at 13:23:31 Jan 03, 20XX
010-001
010-002
010-010
010-011
List Air Sampling – Trip_pts
Press ENTER when the T in TRIP_PTS is
blinking to select LIST AIR SAMPLING
TRIP_PTS.
The System prompts you to select between
ALARM_TRIP and FLOW_TRIP.
Press ENTER when the A in ALARM_TRIP
is blinking to select LIST TRIP_PTS
ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The System displays
the current alarm trip point settings for the
address specified:
010-004 P1: 20%
Print the Air Sampling Alarm Trip Pts
Press PRINT when the A in ALARM_TRIP
is blinking to print the AIR SAMPLING
ALARM_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1 (ASP) module
number and press ENTER. The System
sends alarm trip point levels for all devices
on the selected MODULE to the printer.
Air Sampling Alarm Trip Points at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 30%
010-002 13:23:31 Jan 03,20XX, PRE1: 30% PRE2: 50%
010-010 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 50%
3-34
13:23:31 Jan 03,20XX
0% Scale >> .
. << LOW, Cust Msg 1
13:23:32 Jan 03,20XX
100% Scale >> !
! <<
13:23:31 Jan 03,20XX
42% Scale >> !
. << NORM, Cust Msg 10
13:23:32 Jan 03,20XX
100% Scale >> !
. << NORM, Cust Msg 11
P2: 60%
ALRM: 100%, Cust Msg 1
ALRM: 90%, Cust Msg 2
ALRM: 100%, Cust Msg 10
010-011 13:23:31 Jan 03,20XX, PRE1: 50% PRE2: 80%
ALRM: 100%, Cust Msg 11
Press ENTER when the F in FLOW_TRIP is
HIGH, Cust Msg
blinking to select LIST TRIP_PTS
FLOW_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The System displays
the current air flow trip point settings for the
address specified:
010-004
Print the Air Sampling Flow Trip Pts
Press PRINT when the F in FLOW_TRIP
is blinking to print the AIR SAMPLING
FLOW_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1 (ASP) module
number and press ENTER.
ALM: 90%
The System sends air flow trip point levels
for all devices on the selected MODULE to
the printer.
Air Sampling Air Flow Trip Points at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 90%,
Cust Msg 1
010-002 13:23:31 Jan 03,20XX, LOW: 20% HIGH: 80%,
Cust Msg 1
010-010 13:23:31 Jan 03,20XX, LOW: 30% HIGH: 70%,
Cust Msg 1
010-011 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 80%,
Cust Msg 1

List: Percent/ft

Use List Percent/ft to show settings in
percent/ft obscuration of the ILI and ILP
Series detectors.
From the List menu, use the left or right
arrow key to cause the P in PERCENT/FT
to start blinking:
LOW:
20%
HIGH:
80%