Setting A Non Standard Htl Encoder - Siemens SINAMICS G120D Operating Instructions Manual

Control units, distrubuted converter
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

A.7

Setting a non standard HTL encoder

Proceeding: manually configuring the encoder
1. Set p0010 = 4.
2. Configure the encoder using the table below.
3. Set p0010 = 0.
Parameter
Description
p0400[0]
Encoder type selection (Factory setting: 0)
Selects the encoder from the list of encoder types supported by the firmware of the Control Unit.
0
No encoder
3001
1024 HTL A/B with zero mark
3003
2048 HTL A/B with zero mark
p0408[0]
Rotary encoder pulse No. (Factory setting: 2048)
Sets the number of encoder pulses.
p0410[0]
Encoder inversion actual value (Factory setting: 0000 bin)
Bit 00
1 signal: Invert speed actual value
Bit 01
Not relevant for the CU240D-2
p0425[0]
Encoder, rotary zero mark distance (Factory setting: 2048)
Sets the distance in pulses between two zero marks. This information is used for zero mark monitoring.
p0430[0]
Sensor Module configuration (Factory setting: 0000 0000 0000 0000 0000 0000 0000 0000 bin)
Bit
Signal name
21
A one-off zero mark distance error is tolerated. In the event of a defect, the
fault F3x100/F3x101 does not appear, but alarm A3x400/A3x401 does.
25
Switch-off encoder voltage supply during parking
A bit-wise configuration is only possible if the corresponding property is also present in r0458.
p0437[0]
Sensor Module configuration extended (Factory setting: 0000 0000 0000 0000 0000 1000 0000 0000 bin)
Bit
Signal name
00
Data logger
01
Zero mark edge detection
04
Edge evaluation bit 0
05
Edge evaluation bit 1
06
Freeze the speed actual value for dn/dt errors
11
Fault handling after PROFIdrive
12
Activate additional messages
26
Deselect track monitoring
p0438[0]
Squarewave encoder filter time (Factory setting: 0.64 [μs])
0
No filtering
p0439[0]
Encoder ramp-up time (Factory setting: 0 [ms])
p0453[0]
Pulse encoder evaluation zero speed measuring time (Factory setting: 1000 [ms])
If no pulses are detected from track A/B during this time, a speed actual value of zero is output.
This function is required for slow-running motors so that actual speeds close to zero can be output correctly.
For further information, please refer to the List Manual.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
This allows the encoder parameters to be accessed.
A.7 Setting a non standard HTL encoder
3005
1024 HTL A/B without zero mark
3007
2048 HTL A/B without zero mark
9999
User-defined
Appendix
1 signal
0 signal
Yes
No
Yes
No
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
285