Configuring the fieldbus
7.2 Communication via PROFINET
7.2.3

Configuring communication to the control

Configuring the communication using SIMATIC S7 control
● If the inverter is included in the hardware library of HW-Config, you can configure the
inverter.
● You have the following options, if the inverter is not included in the hardware library:
– Install the more up to date STARTER version
– Install the GSDML of the inverter via "Install options/GSDML file" in HW Config.
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see
Manuals for your converter (Page 292).
Configuring the communication using a non-Siemens control
1. Import the device file (GSDML) of the inverter into the configuring tool of your control
system.
2. Configure the communication.
Installing GSDML
Procedure
To install the GSDML of the inverter into the configuring tool of your control system, proceed
as follows:
1. Load the GSDML to your PC.
– On the Internet: GSDML
– From your inverter:
2. Unzip the GSDML file to a folder on your computer.
3. Import the GSDML into the configuring tool of your control system.
You have now installed the GSDML.
86
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
Insert a memory card into the converter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA