4.2.2

Electrical data

Power Module specifications - 3AC 380 V ... 500 V ± 10 %
Table 4- 1
Product
6SL3525-...
0PE17-5AA1
0PE21-5AA1
0PE23-0AA1
0PE24-0AA1
0PE25-5AA1
0PE27-5AA1
Standby current
If the converter is powered-up, but the motor is still switched off, the converter requires a
standby current.
You have to consider the standby current when calculating the size of the conductors and
selecting the correct protective devices on the line supply.
Table 4- 2
Converter
0.75 - 1.5 kW
3.0 - 4.0 kW
5.5 - 7.5 kW
For more comprehensive information on the standby current, please read the following FAQ:
Standby currents for PM250D
(http://support.automation.siemens.com/WW/view/en/31764702)
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
Rated Output, Input and Fuses
Frame
Rated
HO
size
output
Rated output current
kW
A
A
0.75
2.2
A
1.5
4.1
B
3
7.7
C
4
10.2
C
5.5
13.2
C
7.5
19
Standby currents of the converter
50 Hz
380 V
400 V
0.6
0.63
2.2
2.32
2.9
3.05
Rated input current
A
2.1
3.8
7.2
9.5
12.2
17.7
Standby current (A)
415 V
380 V
0.66
0.7
2.40
2.7
3.15
3.5
Installation
4.2 Electrical Installation
Fuse
3NA3...
A
Type
10
803
-
10
803
-
16
805
-
20
807
-
20
807
-
32
812
-
60 Hz
440 V
480 V
0.8
0.91
3.2
3.33
4.0
4.40
33