Setting The Filter For Safety-Related Inputs - Siemens SINAMICS G120D Operating Instructions Manual

Control units, distrubuted converter
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

8.8.3.6

Setting the filter for safety-related inputs

Procedure
To set the input filter and simultaneity monitoring of the safety-related input, proceed as
follows:
1. Select the advanced settings for STO.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy for the simultaneity monitoring.
4. Close the screen form.
You have set the input filter and the simultaneity monitoring of the safety-related input.
Description of the signal filter
The following are available for the signal processing of the safety-related inputs:
● A tolerance for the simultaneous monitoring.
● A filter to suppress short signals, e.g. test pulses.
A tolerance for the simultaneous monitoring
The inverter checks whether the signals at both inputs always have the same signal status
(high or low).
With electromechanical sensors (e.g. emergency stop buttons or door switches), the two
sensor contacts never switch at exactly the same time and are therefore temporarily
inconsistent (discrepancy). A long-term discrepancy indicates a fault in the wiring of a safety-
related input, e.g. a wire break.
When appropriately set, the inverter tolerates brief discrepancies.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
8.8 Safe Torque Off (STO) safety function
Setting functions
183

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240d-2

Table of Contents