Motorized Potentiometer As Setpoint Source - Siemens SINAMICS G120D Operating Instructions Manual

Control units, distrubuted converter
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Setting functions
8.3 Setpoints
8.3.4

Motorized potentiometer as setpoint source

The "Motorized potentiometer" function emulates an electromechanical potentiometer. The
output value of the motorized potentiometer can be continually set using the "up" and "down"
control signals.
Interconnecting the motorized potentiometer (MOP) with the setpoint source
Figure 8-9
Table 8- 3
Parameter
p1047
p1048
p1040
Table 8- 4
Parameter
p1070 = 1050 Main setpoint
p1035
p1036
Adapting the behavior of the motorized potentiometer
Figure 8-10
116
Motorized potentiometer as setpoint source
Basic setup of motorized potentiometer
Description
MOP ramp-up time (factory setting: 10 s)
MOP ramp-down time (factory setting: 10 s)
MOP start value (factory setting: 0 rpm)
Defines the start value [rpm], which is effective when switching on the motor.
Setting the MOP as setpoint source
Remark
Interconnecting the main setpoint with MOP.
Motorized potentiometer, setpoint higher
Motorized potentiometer, setpoint lower
Function chart of motorized potentiometer
Interconnect these commands with
signals of your choice.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA