Parameter contents
Parameter contents can be parameter values or connectors.
Table 7- 5
Table 7- 6
Telegram examples
Read request: Read out serial number of the Power Module (p7841[2])
To obtain the value of the indexed parameter p7841, you must fill the telegram of the
parameter channel with the following data:
● PKE, bit 12 ... 15 (AK): = 6 (request parameter value (field))
● PKE, bit 0 ... 10 (PNU): = 1841 (Parameter number without offset)
● IND, bit 8 ... 15 (subindex): = 2 (Index of the parameter)
● IND, bit 0 ... 7 (page index): = 90 hex (offset 6000 ≙ 90 hex)
● Because you want to read the parameter value, words 3 and 4 in the parameter channel
Figure 7-4
Telegram for a read request from p7841[2]
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
Parameter values in the parameter channel
PWE, 3rd word
Bit 15 ... 0
0
0
Connectors in the parameter channel
PWE, 3rd word
Bit 15 ... 0
Number of the connector
Parameter number = PNU + offset (page index)
(7841 = 1841 + 6000)
for requesting the parameter value are irrelevant. They should be assigned a value of 0,
for example.
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Bit 15 ... 8
0
32-bit value
Bit 15 ... 10
3F hex
Configuring the fieldbus
PWE, 4th word
Bit 7 ... 0
8-bit value
16-bit value
PWE, 4th word
Bit 9 ... 0
The index or bit field
number of the connector