Status word 3 (ZSW3)
The status word 3 is pre-assigned as follows.
● Bit 0... 15 manufacturer-specific
Bit Value
Significance
0
1
DC braking active
1
1
|n_act| > p1226
2
1
|n_act| > p1080
3
1
i_act ≧ p2170
4
1
|n_act| > p2155
5
1
|n_act| ≦ p2155
6
1
|n_act| ≧ r1119
7
1
DC link voltage ≦ p2172
8
1
DC link voltage > p2172
9
1
Ramping completed
10 1
Technology controller output at lower
limit
11 1
Technology controller output at upper
limit
12
Not used
13
Not used
14
Not used
15
Not used
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Description
--
Absolute current speed > stationary state
detection
Absolute actual speed > minimum speed
Actual current ≥ current threshold value
Absolute actual speed > speed threshold
value 2
Absolute actual speed < speed threshold
value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold value
Actual DC link voltage > threshold value
Ramp-function generator is not active.
Technology controller output ≦ p2292
Technology controller output > p2291
Configuring the fieldbus
Signal interconnection
in the inverter
p2051[3] = r0053