Technical data
12.1 Performance ratings Control Unit
Feature
Fail-safe input
PFH
USB interface
Note
Short-term voltage dips in the external 24 V supply (≤ 3 ms and ≤ 95% of the rated voltage)
When the mains voltage of the inverter is switched off, the inverter responds to short-term
voltage dips in the external 24 V supply with fault F30074. Communication via fieldbus,
however, remains in effect in this case.
254
Specification
DI 4 and DI 5 form the fail-safe digital input.
•
Maximum input voltage 30 V, 5.5 mA
•
Response time:
•
–
Typical: 5 ms + debounce time p9651
–
Typical, if debounce time = 0: 6 ms
–
Worst-case scenario: 15 ms + debounce time
–
Worst case, if debounce time = 0: 16 ms
You will find the extended function data in the Safety Integrated
•
Function Manual.
5 × 10E-8
Probability of failure of the fail-safe functions (Probability of Failure per
Hour)
Mini-B (not available on the push-pull variants of the control unit)
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA