Installing the Rack Terminal Server 48V DC

Installation

The Rack Terminal Server 48V DC is designed for professional installation in a restricted
access area. The installation should comply with current local or national standards
applicable to the territory where the Rack Terminal Server is installed.
Warning
The Rack Terminal Server 48V DC shall be installed in a closed rack system with a power
distribution unit. A listed branch circuit over-current protective devices rated at 3 amps DC
shall be provided either in the power distribution unit or between the power distribution unit
and the Rack Terminal Server.

Electrical Supply Details

The Rack Terminal Server is supplied with an Input Power cable (802-0061). This should be
connected to your 48V DC supply system which should have adequate over-current
protection within the closed rack system and comply with current local or national standards
applicable to the territory.
Warning
This equipment must be earthed for safety and to ensure ESD protection for correct
operation and protection of the internal circuitry.
Connect the input power cable to your over-current protected power distribution unit as
follows:
Red Positive
Black Negative
White Ground/earth