IMPORTANT (FOR EUROPE, ONLY)
To comply with CE requirements, devices with a
voltage in the range of 50...1000 Vac or
75...1500 Vdc which are not provided with a supply
cord and a plug or with other means for discon-
nection from the supply having a contact separation
of at least 3 mm in all poles, must have the means
for disconnection incorporated in the fixed wiring.

Cable Routing

The min. distance to power mains cables is 0.4 in. (10 mm)
for shielded cable and 4 in. (10 cm) for unshielded cable.
All low-voltage signal and output cables should be regarded
as communication circuits in accordance with VDE 0100 and
VDE 0800 (or NEC or other equivalent), and should therefore
be routed separately from mains cables.
Joining sensor cables should be avoided.

Shielding I/O Module, Power Supply Cables

Shielding input and output module and power supply cables
is not necessary if the general guidelines for cable routing are
observed. If, in certain cases, the routing guidelines cannot
be observed, then shielded cable must be used.
The shield must not be terminated at a controller; instead, to
avoid ground loops, the shield must be grounded (at only one
end) at the control panel.
To prevent ground loops, shielding of input/output cables
leading to peripheral devices must be grounded only at the
control panel end.

Shielding of Data-Transmitting Cables

Connect the shield of the system bus (C-Bus) to system
ground on both ends. Each end of the shield on the system
bus should be connected to the system ground terminal of the
respective CPU module. Do not connect it to the control panel
earth or any other earth ground points.
NOTE: The L
W
bus must not be grounded on the
ON
ORKS
CPU side.
To connect remote operator interface units, ready-made
cables are available (XW565; XW582, XW583, etc.) with the
shield already connected to the CPU module plug end.

Grounding (XC5010C / XC6010, only)

The controller should be grounded using as short a cable as
possible (min. 16 AWG [1.5 mm²]) between the control panel
and terminal 3 of the power supply module.

System Ground

WARNING
High voltage
Risk of electrical shock or equipment damage.
The controller's system ground must have no
connection with the control cabinet ground!
EXCEL 500/600 - INSTALLATION INSTRUCTIONS
NOTE: A document providing additional information on
system grounding (if required) is available via the
Honeywell Technical Assistance Center (TAC) or, for
Honeywell employees, on the Docu Server under:
http://web.ge51.honeywell.de/dep/mc/TAC_Tips.

RFI Suppression

Honeywell actuators are RFI (Radio Frequency Interference)
suppressed as standard in accordance with VDE 0871/B and
VDE 0875/N.

XC5010C/XC6010 Cable Lengths and Sizes

Table 3. Cable sizing (use only copper cables)
type of signal
 300 ft
(100 m)
24 Vac power
16 AWG
supply
(1.5 mm
low voltage
signals*
*0...10 V sensors, totalizers, digital inputs, 0 to 10 V signals for
actuators, etc.
PRIMARY
VOLTAGE
GND
24 Vac
GND
24 Vac
TRANSFORMER
Fig. 41. Power for XC5010C/XC6010 (XP502 power supply
module) with 24 V actuator
A cable length of 1300 ft (400 m) with a cross sectional area
2
of 0.75 mm
(18 AWG) is permissible for a two-core,
0...10 Vdc signal cable.
For cable lengths exceeding 1300 ft (400 m) between the
transformer and the field device, see NOTE in section
"System Ground".

Lightning Protection

Please contact your local Honeywell representative for
information on lightning protection.
17
cross-sectional area
 550 ft
(170 m)
14 AWG
2
2
)
(2.5 mm
)
14 – 18 AWG (2.5 – 0.75 mm
max. 400 m
min. 0.75 mm 2
Y (0...10 Vdc)
GND
24 Vac
EN1R-1047GE51 R0913
 1300 ft
(400 m)
-
2
)