This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you are installing a IFP-300/ECS panel for the first time.

3.1 Inventory

When an IFP-300/ECS shipment is received, check that all the parts have been included in the shipment. The shipment consist of one of
each of the following:
main circuit board with display
backbox with door.
plastic bag containing two keys, screws, cables, and ten 4.7k ohm end-of-line resistors.
manual

3.2 Environmental Specifications

It is important to protect the IFP-300 control panel from water. To prevent water damage, the following precaution should be FOL-
LOWED when installing the units:
Mount indoors in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the IFP-300 control panel, the unit should be mounted where it will NOT be exposed to temperatures
outside the range of 0°C-49°C (32°F-120°F) or humidity not exceeding 93% noncondensing.

3.3 Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions about software and the appropriate version for a specific application. Software updates can be
found at www.farenhyt.com

3.4 Electrical Specifications

Table 3.1 list the terminal block on the IFP-300 as well as a description of the each individual terminal and their respective electrical rat-
ing.
Terminal No.
Terminal Block 1
Terminal Block 2
Terminal Block 3
9

Section 3: Before You Begin Installing

Label
Group
Individual
TELCO 1
RING
TIP
PHONE 1
RING
TIP
TELCO 2
RING
TIP
PHONE 2
RING
TIP
SLC IN
+
SLC OUT
+
SLC PROG
+
SBUS Out
B
A
+
Table 3.1 Terminal Descriptions and Electrical Specifications
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Description
Phone Line 1 Telco Ring
Phone Line 1 Telco Tip
Phone Line 1 Phone Ring
Phone Line 1 Phone Tip
Phone Line 2 Telco Ring
Phone Line 2 Telco Tip
Phone Line 2 Phone Ring
Phone Line 2 Phone Tip
Used for Class A installations
SLC terminals
Used for programming SLC
Detectors
SBUS Communication
SBUS Power
Rating
Voltage
Current
32 VDC
150 mA
32 VDC
150 mA
32 VDC
150 mA
5 VDC
100 mA
24 VDC
1.0 A