Magnetic Pickup (Mpu) Input (Option M4) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

6.1.20 Magnetic pickup (MPU) input (option M4)

Magnetic pickup (MPU)
MPU
Output
100
101
NPN sensor
NPN
+12/24V DC
+V DC
Output
0V DC
0V DC
C = 22 nF, 100 V foil type
R = 1200 Ω @ 24 V DC, 600 Ω @ 12 V DC
PNP sensor
PNP
+V DC
+12/24V DC
Output
R
0V DC
0V DC
C = 22 nF, 100 V foil type
R = 1200 Ω @ 24 V DC, 600 Ω @ 12 V DC
Charger, W output
Charger
C
W
C = 22 nF, 100 V foil type
DEIF A/S
Multi-line 2
Multi-line 2
R
C
100
C
101
Multi-line 2
C
100
C
101
Multi-line 2
100
101
Wirings
Page 55 of 64