6.1.21 Analogue inputs (option M15.x)

The analogue 0(4) to 20 mA inputs are passive and require an external power supply:
Inputs
+
-
-
or
Inputs
+
+
-
-

6.1.22 Stop coil with wire break detection (option M4)

+12/24V DC
Multi-line 2
123
124
A1
Stop coil
A2
0V DC
To avoid faulty activation of the stop coil caused by the wire break circuit, use a stop coil with
the following specifications:
24 V DC: I
>10 mA/R
ON
12 V DC: I
>10 mA/R
ON
Remember to mount the free wheel diode.

6.1.23 Transistor outputs

The open collector outputs can be used as kWh and kVArh counter outputs or as relay outputs. The outputs
are low power outputs. For that reason, one of the following circuits must be applied.
DEIF A/S
24V DC supply
Transmitter
+
24V DC supply
Transmitter
<1650 Ω
COIL
<800 Ω
COIL
+
-
+
-
Wirings