Digital Inputs - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK
Option M14.8
4 × relay outputs.
Term.
Function
126
Relay 126
250 V AC, 8 A max.
127
128
Relay 128
250 V AC, 8 A max.
129
130
Relay 130
250 V AC, 8 A max.
131
132
Relay 132
250 V AC, 8 A max.
133
Option M15.8
4 × analogue 4 to 20 mA inputs.
Term.
Function
126
Input 127 common
127
Analogue input 127+
128
Input 129 common
129
Analogue input 129+
130
Input 131 common
131
Analogue input 131+
132
Input 133 common
133
Analogue input 133+

5.1.9 Digital inputs

Term. Name
23
Alarm inhibit 1/configurable
24
Remote alarm acknowledge/configu-
rable
25
Configurable/start sync./control (op-
tion G2)
26
Configurable/GB open (option G2)
27
Configurable/GB closed (option G2)
DEIF A/S
Function
External input for inhibit of selected alarms
Option G2: Activates synchronisation. The Deload function
is used to open the breaker
Option G2: Breaker feedback signal. The connection
breaker is in position OFF
Option G2: Breaker feedback signal. The connection
breaker is in position ON
Description
Configurable
Configurable
Configurable
Configurable
Description
Common
4 to 20 mA in
Common
4 to 20 mA in
Common
4 to 20 mA in
Common
4 to 20 mA in
Page 24 of 64
I/O lists