Slot #5, Ac Measuring; Slot #6, I/O Extension (Optional) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.1.5 Slot #5, AC measuring

Terminal
Function
73
I L1 s1
74
I L1 s2
75
I L2 s1
76
I L2 s2
77
I L3 s1
78
I L3 s2
79
U L1
80
Not used
81
U L2
82
Not used
83
U L3
84
U neutral
85
U L1
86
Not used
87
U L2
88
U neutral
89
U L3
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are
available (phase-to-phase) from 100 V AC to 690 V AC.

5.1.6 Slot #6, I/O extension (optional)

Option F1
Transducer output card.
Term.
Function
90
Not used
91
0
92
0(4) to 20 mA out
93
Not used
94
Not used
95
0
96
0(4) to 20 mA out
97
Not used
DEIF A/S
Technical data
Generator current L1
Generator current L2
Generator current L3
Generator voltage L1
Generator voltage L2
Generator voltage L3
Generator voltage neutral
Bus voltage L1
Bus voltage L2
Bus voltage neutral
Bus voltage L3
Description
Analogue output 91, selectable
Analogue output 95, selectable
Description
1/5 A AC input
1/5 A AC input
1/5 A AC input
Max. 690 V AC phase-phase value
Max. 690 V AC phase-phase value
Max. 690 V AC phase-phase value
Max. 690 V AC phase-phase value
Max. 690 V AC phase-phase value
Max. 690 V AC phase-phase value
I/O lists
Page 20 of 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpc-3 hydroGpu-3 gasGpu-3Gpu-3 hydroGpc-3 gasPpu-3