Slot #3, Digital I/Os - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.2.3 Slot #3, digital I/Os

Terminal
Function
37
-5 to 0 to 5 V DC
38
Com.
39
-5 to 0 to 5 V DC
40
-10 to 0 to 10 V DC
41
Com.
42
-10 to 0 to 10 V DC
43
Digital input
44
Digital input
45
Digital input
46
Digital input
47
Digital input
48
Digital input
49
Digital input
50
Digital input
51
Digital input
52
Digital input
53
Digital input
54
Digital input
55
Digital input
56
Com.
57
NO
58
Com.
59
NO
60
Com.
61
NO
62
Com.
63
NO
64
Com.
AVR control requires option D1.
DEIF A/S
Technical data
Description
Analogue I/O
Active load sharing line
Common
Common for load sharing lines
Analogue I/O
Reactive load sharing
Analogue input
f/P set point (passive)
Common
Common for 40/42
Analogue input
U/Q set point (passive)
Optocoupler
Deload/configurable
Optocoupler
Man. GOV UP/configurable
Optocoupler
Man. GOV DOWN/configurable
Optocoupler
Man. AVR UP/configurable
Optocoupler
Man. AVR DOWN/configurable
Optocoupler
Fixed frequency/configurable
Optocoupler
P load sharing/configurable
Optocoupler
Ext. GOV set point/configurable
Optocoupler
Fixed voltage/configurable
Optocoupler
Q load sharing/configurable
Optocoupler
Ext. AVR set point/configurable
Optocoupler
Configurable
Optocoupler
Configurable
Common
Common for terminals 43-55
Relay 57 6
GOV/AVR control or configurable
250 V AC/8 A
Relay 59 7
GOV/AVR control or configurable
250 V AC/8 A
Relay 61 8
GOV/AVR control or configurable
250 V AC/8 A
Relay 63 9
GOV/AVR control or configurable
250 V AC/8 A
I/O lists
Page 29 of 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpc-3 hydroGpu-3 gasGpu-3Gpu-3 hydroGpc-3 gasPpu-3

Table of Contents