I/O Lists; I/O List And Terminal Strip Description - Gpu, Gpu Hydro; Slot #1, Power Supply And Binary I/O - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5. I/O lists

5.1 I/O list and terminal strip description - GPU, GPU Hydro

5.1.1 Slot #1, power supply and binary I/O

For the relay outputs, the following terms will be used:
NO means Normally Open
NC means Normally Closed
Com. means common terminal for the relay in question
Terminal Function
1
+12/24 V DC
2
0 V DC
3
NC
4
Com.
5
NO
6
Com.
7
NC
8
NO
9
Com.
10
NC
11
NO
12
Com.
13
NC
14
NO
15
Com.
16
NC
17
NO
18
Com.
19
NC
20
Open collector 1 Transistor out (relay 20) Configurable as standard relay output
21
Open collector 2 Transistor out (relay 21) Configurable as standard relay output
22
Com.
23
Digital input
24
Digital input
25
Digital input
26
Digital input
27
Digital input
28
Com.
DEIF A/S
Technical data
8 to 36 V DC
Status relay
24 V/1 A
Relay 5
250 V AC/8 A
Relay 8
250 V AC/8 A
Relay 11
250 V AC/8 A
Relay 14
250 V AC/8 A
Relay 17
250 V AC/8 A
Common
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Common
Description
Power supply
Normally closed relay, processor/power supply
status supervision
Alarm horn/configurable
Configurable
Configurable
Open GB
Configurable
Common terminal for terminals 20 and 21
Alarm inhibit 1/configurable
Remote alarm acknowledge/configurable
Configurable
Configurable
Configurable
Common for terminals 23-27
I/O lists
Page 13 of 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpc-3 hydroGpu-3 gasGpu-3Gpu-3 hydroGpc-3 gasPpu-3

Table of Contents