ML-2 installation instructions 4189340582
UK

5.1.4 Slot #4, GOV/AVR (optional)

GOV control requires option G2.
AVR control requires options G2 and D1.
Option M14.4
GOV/AVR or configurable relay output card.
Term.
Function
65
Relay 65
250 V AC/8 A
66
67
Relay 67
250 V AC/8 A
68
69
Relay 69
250 V AC/8 A
70
71
Relay 71
250 V AC/8 A
72
Option E1
GOV/AVR or transducer output card.
Term.
Function
65
Not used
66
+/-20 mA out
67
0
68
Not used
69
Not used
70
+/-20 mA out
71
0
72
Not used
DEIF A/S
Description
GOV/AVR or configurable
GOV/AVR or configurable
GOV/AVR or configurable
GOV/AVR or configurable
Description
Speed governor/AVR set point output or transducer
(Analogue output 66)
Speed governor/AVR voltage set point output or transducer
(Analogue output 70)