Digital Inputs - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.2.9 Digital inputs

Term. Name
23
Alarm inhibit 1/configurable
24
Remote alarm acknowledge/config-
urable
25
Start sync./control/configurable
26
GB open
27
GB closed
43
Deload/configurable
44
Manual GOV UP/configurable
45
Manual GOV DOWN/configurable
46
Manual AVR UP/configurable
47
Manual AVR DOWN/configurable
48
Fixed frequency/configurable
49
P load sharing/configurable
50
Ext. GOV set point/configurable
51
Fixed voltage/configurable
52
Q load sharing/configurable
53
Ext. AVR set point/configurable
54
Configurable
55
Configurable
DEIF A/S
Function
External input for inhibit of selected alarms
Remote alarm acknowledge
Activates the regulation and synchronisation. Works togeth-
er with "Deload" (43)
Breaker feedback signal. The connection breaker is in posi-
tion OFF
Breaker feedback signal. The connection breaker is in posi-
tion ON
Activates the deload sequence. Works together with start
sync./control (25)
Increase engine speed
Decrease engine speed
Option D1: Increase generator voltage
Option D1: Decrease generator voltage
Activates frequency controller
Activates load sharing controller
The nominal frequency set point will be controlled from the
analogue inputs terminal 40/41. The internal set point will
not be used
Activates voltage controller
Activates Q load sharing controller
The nominal voltage set point will be controlled from the an-
alogue inputs terminal 41/42. The internal set point will not
be used