ML-2 installation instructions 4189340582
UK

6.1.15 Electronic speed governor

Multi-line 2
66
Output for
speed governor
67
If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 Ω will
convert the +/-20 mA into +/-5 V DC).
For further information on how to connect the analogue output to the most common speed
governors, please refer to:
Application Notes, Interfacing DEIF equipment to governors and AVRs, document number
4189340670 at www.deif.com.

6.1.16 AVR with analogue outputs

Multi-line 2
70
Output for
AVR
71
If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 Ω will
convert the +/-20 mA into +/-5 V DC).
For further information on how to connect the analogue output to the most common AVRs,
please refer to:
Application Notes, Interfacing DEIF equipment to governors and AVRs, document number
4189340670 at www.deif.com.
DEIF A/S
±20 mA
0
±20 mA
0
Wirings