ML-2 installation instructions 4189340582
UK

6.1.13 Mechanical speed governor

The illustration below shows the necessary connections to carry out speed control using relay outputs.
Multi-line 2
68
Speed lower
67
66
Speed raise
65
Ø
Supply for
Pilot motor
In order to extend the lifetime of the internal relays and prevent unwanted switching noise, it is recommended
to use free wheel diodes (1N4007), if a DC voltage is used for the regulation. If an AC voltage is used for the
regulation, it is recommended to use a varistor. The diode/varistor must be placed across the terminals of the
pilot motor/external regulation relay coil.

6.1.14 AVR with relay outputs

Multi-line 2
71
Voltage lower
72
69
Voltage raise
70
Supply for
AVR voltage
DEIF A/S
Lower
speed
Pilot
motor
Raise
speed
Ø
AVR
Lower Voltage
Raise Voltage
Common
Ø
Ø
control
Wirings