ML-2 installation instructions 4189340582
UK

6.1.24 Additional display unit, DU-2 (option X2)

Standard display DU-2
AOP-1
ML - 2
OFF
CAN 1
CAN 2
ON
Terminal block
2
1
1...6
6 - Black: GND
5 - Black/White: +5 VDC
4 - Brown: Not used
3 - Red: CAN L
2 - Brown/white: CAN GND
1 - Red/white: CAN H
Left CAN port (CAN 1)
End resistor:
2 units connected:
3 units connected:
The maximum length of the CAN bus line is 200 m.
A DC/DC converter for the DC supply voltage and 2 × 1 m cable with an RJ45 plug in one end
and stripped wires in the other end are included in the DU-2 (option X2) delivery.
DEIF A/S
Additional standard display DU-2
OFF
CAN 1
ON
2
1
Cable shield
1...6
6 - Not used
5 - Not used
4 - Not used
3 - Red: CAN L
2 - Brown/white: CAN GND
1 - Red/white: CAN H
Right CAN port (CAN 2)
Dip switch no. 1 has to be set to ON on both units.
Dip switch no. 1 has to be set to ON on unit 1 and unit 3.
CAN 2
-
+
5V DC
DIN Rail
24V DC
+ -
Wirings
Page 58 of 64