Slot #2, External Communication (Optional) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.2.2 Slot #2, external communication (optional)

Option H2 (Modbus RS-485)
Terminal
29
30
31
32
33
34
35
36
The serial communication line should be terminated between DATA + and DATA - with a resis-
tor equal to the cable impedance. The terminals 29/33 and 31/35 are internally connected.
Option H3 (Profibus DP)
Terminal
Function
29
DATA + (B)
30
GND
31
DATA - (A)
32
DATA + (B)
33
GND
34
DATA - (A)
35
Not used
36
Not used
Option H8.2
CAN bus interface for external I/O modules.
Terminal
Function
29
Not used
30
Not used
31
CAN-L
32
Not used
33
CAN-H
34
CAN-L
35
Not used
36
CAN-H
DEIF A/S
Function
DATA + (A)
Not used
DATA - (B)
Not used
DATA + (A)
Not used
DATA - (B)
Not used
Description
CAN bus communication for Beckhoff external I/O modules
Description
Modbus RTU/ASCII, RS-485
Description
Pin 3 on 9-pole sub-D connector
Pin 5 on 9-pole sub-D connector
Pin 8 on 9-pole sub-D connector
I/O lists
Page 27 of 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpc-3 hydroGpu-3 gasGpu-3Gpu-3 hydroGpc-3 gasPpu-3

Table of Contents